Ventilation
MDDS / MDCS models are thought to be installed directly in the room to be dehumidified and the pleasant design is suitable also for other ambiences, such as museum, archives, libraries, churches, cellars and basements. The sober but elegant look eases the installation in public and private ambiences, generally characterized by a sophisticated design.
The dehumidifiers are designed for installation on the wall, floor (MDDS) or in utility rooms (MDCS) adjacent to the one being dehumidified. The series is comprised of 10 models with their dehumidification capacity ranging from 46 to 290 l/day. With their practical design, they are also suitable for other applications, such as museums, archives, churches, cellars and basements. The attractive design of the dehumidifiers will suit both public and private rooms.
Legend:
А – Grilles
B – Wall duct plenum
C – Air supply plenum
D – Return plenum
MDDS / MDCS dehumidifiers with advanced control* are completely autonomous in managing humidity: the control on board reads the ambient humidity and activates the dehumidification process when necessary. Finally, the installation of these units is particularly simple.
*sold separately
Unit allows to control relative humidity through probes on the display.
Unit could function in three modes:
Ventilation has three speeds and it is automatically managed depending on active request. It is present a clock card with time bands: 7 daily programs, 24 time bands per day, settable parameters: unit on / off, humidity and temperature. User terminal could be remote, unit will install an on board temperature and humidity probe, a cable for installation of remote user terminal is supplied (optional).
Mycond informs that quick choice graphs are only exemplificative.
Specifications | Units | MDDS - MDCS 04 |
MDDS - MDCS 05 |
MDDS - MDCS 06 |
MDDS - MDCS 07 |
MDDS - MDCS 09 |
MDDS - MDCS 10 |
MDDS - MDCS 16 |
MDDS - MDCS 19 |
MDDS - MDCS 21 |
MDDS - MDCS 23 |
MDDS - MDCS 30 |
Dehumidifying capacity | L/Day | 46 | 52 | 62 | 68 | 89 | 98 | 165 | 186 | 211 | 226 | 290 |
Refrigerant | Type | R410A | R410A | R410A | R410A | R410A | R410A | R410A | R410A | R410A | R410A | R410A |
Air flow |
m3/h |
350 | 450 | 500 | 600 | 700 | 800 | 1000 | 1200 | 1500 | 1500 | 2000 |
Available static pressure | Pa | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 |
Hot water coil capacity* | kW | 3,7 | 4,5 | 4,8 | 6,1 | 6,8 | 7,5 | 10,1 | 11,5 | 14,5 | 14,5 | 17 |
Electrical heaters capacity* | kW | 1 | 1 | 1,5 | 2 | 3,2 | 3,2 | 4 | 4 | 7,2 | 7,2 | 7,2 |
Power supply | V/ph/Hz | 230 / 1+N / 50 | 400 / 3+N / 50 | |||||||||
Sound level | dB(A) | 43 | 45 | 46 | 47 | 48 | 49 | 51 | 53 | 54 | 55 | 57 |
Dimensions LxPxH | mm | 850x280x780 | 1050x280x780 | 1350x330x850 | 1550x330x850 | |||||||
Weight | kg | 46 | 46 | 46 | 55 | 55 | 55 | 88 | 88 | 100 | 100 |
102 |
*optionally available
All the values refer to the following conditions: inlet air: 30°C - 80% RH; inlet/outlet water: 80/70°C