Ventilation
It is ideal for production processes, laboratories, medical facilities, datа centers and other facilities that require year-round cooling. Adjusting the output temperature of the coolant and the algorithm for accurate maintenance of the specified setpoint will ensure long and reliable operation of your equipment.
The modular heat pump MCU-YHA is specifically designed for year-round cooling at outdoor air temperatures from -20 °C to 48 °C.
The air heat exchanger fans are equipped with brushless EC motors. The motor speed is adjustable between 20% and 100% to safely provide the necessary condensing pressure.
Specifications | Units | MCU066YHA |
Cooling capacity | kW | 66 |
Heating capacity | kW | 70 |
Capacity steps | % | 0/50/100 |
Power supply | 380-415 V, 3 phases, 50 Hz | |
Electric power in the cooling mode EER |
kW W/W |
21,29 3,1 |
Electric power in the heating mode COP |
kW W/W |
21,85 3,2 |
Refrigerant type | R410A | |
Compressor type | Hermetic scroll compressor | |
Number of compressors | 2 | |
Water flow rate | m3/h | 11,4 |
Water perssure drop | kPa | 45 |
Hydraulic connection | DN 65 | |
Air heat exchanger type | Copper and aluminium | |
Fan type | Axial | |
Number of fans | 2 | |
Air flow rate | m3/h | 26000 |
Dimensions, LxWxH | mm | 2200x860x1980 |
Weight | kg | 620 |
Notes:
1. Cooling capacity and electric power consumption during cooling operation refer to the rated water flow rate, outlet water temperature 7 °C and ambient air temperature 35 °C.
2. Heating capacity and electric power consumption during heating operation refer to the rated water flow rate, outlet water temperature 45 °C and ambient air temperature 7 °CDB.