Ventilation
High-efficiency air dehumidifiers MSTR / MSPR are designed for comprehensive control of temperature, humidity, heat recovery and ambient air conditioning in roofed swimming pools and corrosive environments.
The mixed-flow plate heat recuperator allows recovering heat from the exhaust air, which is used to heat up the supply air. Pool version (standard): aluminium fins with protective coating.
Remote air condenser (for MSTR models, max. distance 30 m). The condenser dissipates the heat produced during dehumidification into the outdoor environment to prevent the ambient from overheating. The unit is used as an air conditioner.
The desuperheater connected in series to the compressor allows reducing the air temperature at the discharge into the pool, while recovering the refrigerant superheating energy by heating the water. It is available in versions designed either for process or chlorinated water (stainless steel AISI 316L).
Legend:
The MSPR / MSTR units are ideal for swimming pools that not only require dehumidification but must also renew the indoor air without dispersing heat outdoors. The units of the MSPR / MSTR series are designed for use in small, medium and large swimming pools, where regulation of the humidity level and/or prevention of condensation phenomena is required, where a constant air exchange is necessary, even with 24-hour operation. The high efficiency recuperator guarantees efficiencies of up to 80% and the structure is particularly suitable for environments where there is the presence of corrosive substances such as chlorine.
The MSPR/MSTR range uses only EC radial fans with built-in inverters with high energy efficiency. Mycond has developed sophisticated adjustment software to set, measure and control the air flow rate of the MSPR/MSTR dehumidifiers, eliminating any problems arising from incorrect calculation of the pressure drop in the ducting, thus making the installation of the dehumidifier and the commissioning of the system extremely simple and fast, reducing installation time and costs. These units are designed to be connected to rigid ducting. The series consists of 20 models, ranging from 100 L/day and 900 m3/h to 4.600 L/day and 35.000 m3/h.
*3, 4 Including condensate tray and insulation.
* It is possible to install only one water coil; for size up to 0300, on/off three-ways valve.
WINTER: start up, no occupants, covered pool, heating with hot water coil.
Compressor: OFF
Hot water coil: ON (optional)
Desuperheater: OFF (optional)
Remote condenser: OFF (MSPR models)
External air: OFF
WINTER: normal operation, pool open, dehumidification.
Compressor: ON
Hot water coil: OFF (optional)
Desuperheater: OFF (optional)
Remote condenser: OFF (MSPR models)
External air: ON
SPRING, AUTUMN: normal operation, pool open, dehumidification with heat recovery (desuperheater)
Free cooling operation mode available (optional).
Compressor: ON
Hot water coil: OFF (optional)
Desuperheater: ON (optional)
Remote condenser: OFF (MSPR models)
External air: ON
SUMMER: normal operation, pool open, dehumidification and cooling (remote condenser)
Compressor: ON
Hot water coil: OFF (optional)
Desuperheater: OFF (optional)
Remote condenser: ON (MSPR models)
External air: ON
* For an optional electric heater, contact the manufacturer’s sales office.
Specifications | Units | MSTR/MSPR | |||||||||
0100 | 0130 | 0160 | 0190 | 0210 | 0260 | 0300 | 0350 | 0450 | 0580 | ||
Dehumidifying capacity1 | L/Day | 100 | 128 | 157 | 190 | 210 | 268 | 302 | 358 | 452 | 581 |
Recirculation air flow rate | m3/h | 900 | 1200 | 1600 | 1600 | 2000 | 2800 | 2800 | 3800 | 4000 | 4800 |
Fresh air flow rate | kW | 0 - 900 | 0 - 1200 | 0 - 1200 | 0 - 1200 | 0 - 2000 | 0 - 2000 | 0 - 2000 | 0 - 2000 | 0 - 2000 | 0 - 2000 |
Hot water coil capacity1 | kW | 5,5 | 9,8 | 9,8 | 9,8 | 16,5 | 17 | 17 | 26,5 | 26,5 | 27 |
Heat recovery system efficiency2 | % | 70 | 70 | 70 | 70 | 70 | 70 | 70 | 70 | 70 | 70 |
Electric power supply | V/ph/Hz | 230 / 1+N / 50 | 400 / 3+N /50 | ||||||||
Dimensions, L x P x H | mm | 550 x 1452 x 1320 | 850 x 1452 x 1320 | 850 x 1682 x 1769 | |||||||
Weight | kg | 155 | 155 | 160 | 165 | 200 | 210 | 220 | 250 | 270 | 300 |
Specifications | Units | MSTR/MSPR | |||||||||
0750 | 0950 | 1100 | 1400 | 1500 | 1700 | 1900 | 2200 | 3000 | 4500 | ||
Dehumidifying capacity1 | L/Day | 760 | 955 | 1120 | 1380 | 1480 | 1710 | 1870 | 2180 | 2960 | 4650 |
Recirculation air flow rate | m3/h | 7000 | 8200 | 11000 | 12500 | 13000 | 15000 | 15000 | 17000 | 20000 | 35000 |
Fresh air flow rate | kW | 0 - 6000 | 0 - 6000 | 0 - 11000 | 0 - 12500 | 0 - 13000 | 0 - 15000 | 0 - 15000 | 0 - 17000 | 0 - 20000 | 277 |
Hot water coil capacity1 | kW | 48 | 55 | 76 | 83 | 98 | 107 | 107 | 118 | 168 | 235 |
Heat recovery system efficiency2 | % | 70 | 70 | 70 | 70 | 70 | 70 | 70 | 70 | 70 | 235 |
Electric power supply | V/ph/Hz | 400 / 3+N / 50 | |||||||||
Dimensions, L x P x H | mm | 1400 x 2331x 1950 | 2700 x 1950x 2340 | 2500 x 2505 x 2380 | 2500 x 3390 x 2380 |
2500 x 4430 x 2380 |
|||||
Weight | kg | 710 | 730 | 870 | 1060 | 1280 | 1280 | 1290 | 1290 | 1680 | 2100 |
1. Inlet air: 30°C - 80% RH; inlet/outlet water: 80/70°C; outdoor air: 30°C - 50% RH; 100% recirculation.
2. Indoor air: 26°C - 60% RH; outdoor air: -5°C - 80% RH.
Note:
MSTR – standard (industrial) version
MSPR – pool water version