Ventilation
Mycond MSHA(C) is comprehensive solution for indoor swimming pool environment control. Monitoring and regulating humidity and air temperature, is suitable for private or bigger pools, wellnesses and hot tubs. Operating on the condensation principle, it provides constant, reliable and highly effective dehumidifying with the highest efficiency. Its low sound emisions and exclusive design makes Mycond MSHA(C) top innovative solution for indoor pools.
The dehumidifiers of MSHA(C) series are equipped with three air filtering stages. Having passed the first two filtering stages, the purified air passes through the evaporator, where the moisture condenses and drains away, so that the air is dehumidified. After that, the dry air goes through the condenser, where it heats up, and then passes through the final filtering stage (HEPA filter)* to remove the remaining germs and bacteria.
Download the free app for control
MSHA(С) is a product line of swimming pool dehumidifiers by Mycond designed to cover full requirements of domestic pool or spa sizes. As innovative and visually attractive solution for highly effective humidity extraction, they are well known for their best-in-class efficiency that ultimately results in a reduction of unnecessary and preventable costs.
Humidity is not an enemy when is controlled but can cause serious troubles otherwise. Ideal humidity for pool or spa users is when they feel comfortable. This feeling is achieved by a relative humidity from 50% to 65%. Humidity above 70% is detected by condensation on windows and walls and continuously deteriorates the pool or spa environment. It is also a perfect environment for mould and bacteria to grow. Humidity lower than 45% actually causes a reversed problem to bathers in the form of dry feeling and possible harm to mucous tissue. The innovative series of Mycond dehumidifiers keep the humidity at ideal 50%-65%.
Mycond MSHA(С) dehumidifier has fresh air supply possibility. The air inlet is located a side of return air duct, that way the incoming fresh air is effectively preheated by the return air.
The galvanized germicidal UV lamp can only sterilize the place that is exposed to the UV light. Therefore, it is installed at the air supply side, upstream the Н13 filter.
The service door is located on the left (as a standard). With its clever design, the door provides easy access to every part of the equipment.
Specifications | Units | MSHA(C) 28 |
MSHA(C) 40 |
MSHA(C) 60 |
MSHA(C) 100 |
MSHA(C) 140 |
MSHA(C) 180 |
MSHA(C) 250 |
MSHA(C) 380 |
MSHA(C) 500 |
MSHA(C) 750 |
MSHA(C) 1000 |
Dehumidification capacity | l/day | 28 | 40 | 60 | 100 | 140 | 180 | 250 | 380 | 500 | 750 | 1000 |
Air flow rate |
m3/h |
280-350 | 500-670 | 650-780 | 1000- 1200 |
1200- 1350 |
1800- 2200 |
2500- 2900 |
3500- 3850 |
4800- 5300 |
7500- 9000 |
9000- 11000 |
Fan speed |
variable speed 1 speed / variable speed (as an option) |
|||||||||||
External fan pressure | Pa | 100 | 100 | 100 | 100 | 100 | 200 | 200 | 200 | 200 | 400 | 400 |
Recirculation air flow rate |
m3/h |
140-175 | 350-460 | 470-550 | 680-800 | 750-850 | 1200-1450 | 1850- 2050 |
2600- 2850 |
3530- 3900 |
5500- 6500 |
6800- 8100 |
Fresh air flow rate |
m3/h |
140-175 | 150-210 | 180-230 | 320-400 | 400-500 | 600-750 | 650-850 | 900-1000 | 1250-1450 | 2000- 2500 |
2200- 2900 |
Power consumption | W | 420 | 670 | 740 | 1050 | 1300 | 3000 | 4200 | 6600 | 10 000 | 17 000 | 23 500 |
Current | А | 1,9 | 3 | 3,5 | 4,9 | 6,2 | 5,4 | 7,5 | 11,8 | 18 | 30 | 40 |
Power supply | V/Hz | 220/50 | 220/50 | 220/50 | 220/50 | 220/50 | 380/50 | 380/50 | 380/50 | 380/50 | 380/50 | 380/50 |
Controller | touch panel, LCD screen | |||||||||||
Noise level | dB | <35 | <45 | <45 | <45 | <45 | <55 | <55 | <55 | <55 | <55 | <55 |
Refrigerant | R134A | R134A | R134A | R410A | R410A | R410A | R410A | R410A | R410A | R410A | R410A | |
Condenser | copper tubes with blue hydrophile-coated aluminium fins | |||||||||||
Drainage tube | DN20 | DN20 | DN20 | DN20 | DN20 | DN32 | DN32 | DN32 | DN32 | DN32 | DN32 | |
Filter | G4+F7+H13 | 1000G4+F7+H13 (available as option) | ||||||||||
Fresh air duct | mm | Ø100 | Ø100 | Ø100 | Ø150 | Ø150 | 230*230 | 230*230 | 280*280 | 280*280 | 320*320 | 320*320 |
Recirculation air duct | mm | Ø100 | Ø150 | Ø150 | Ø200 | Ø200 | 500*400 | 500*400 | 750*450 | 750*450 | 1200*450 | 1200*450 |
Intake air duct | mm | Ø100 | Ø150 | Ø150 | Ø200 | Ø200 | 356*313 | 356*313 | 818*313 | 818*313 | 1058*348 | 1058*348 |
Dimensions | mm | 830×433×285 | 950×539×265 | 1030×639×375 | 1370×820×640 | 1370×1120×720 | 1700×1642×720 | |||||
Weight | kg | 40 | 45 | 47 | 68 | 71 | 175 | 182 | 270 | 300 | 500 | 560 |
* HEPA filter available as an option